The TANDA WCB-10 has a maximum protection radius of 35 meters.
The automatic tracking and positioning feature utilizes ultraviolet and infrared sensing technologies to detect early fires and accurately locate the fire source for effective extinguishing.
The TANDA WCB-10 weighs 13 kg.
The installation height for the TANDA WCB-10 ranges from 6 to 15 meters.
The fire response time for the TANDA WCB-10 is less than or equal to 30 seconds.
The maximum monitoring radius of the TANDA WCB-10 is 39 meters.
The preset pressure is 0.6 MPa and the working pressure is 0.8 MPa.
The TANDA WCB-10 supports hanging installation.
The elevation angle is adjustable up to 30° and the depression angle is adjustable up to 90°.
The horizontal rotation range of the TANDA WCB-10 is adjustable from 0 to 360°.
The monitor consumes 1W and the scanning feature consumes 40W.
The TANDA WCB-10 can operate in temperatures ranging from 4 to 55°C with humidity levels up to 95% RH non-condensing.
The interface diameter for the TANDA WCB-10 is DN 32.
Yes, the TANDA WCB-10 can be manually operated in addition to its automatic functions.
The TANDA WCB-10 complies with the executive standard for automatic tracking and positioning jet fire extinguishing systems (GB 25204-2010).